Product Overview
The SCAL unit begins the 30 s self-calibration process the first time current is applied in the operating range. The threshold is then set. Subsequent calibrations may be performed by moving SW1 to the position opposite of its current position with or without current applied (hands can be safely away from live voltage). Once current begins flowing, or if it already is, the calibration process will begin. At the end of the 30 seconds, amperage will be read and set as the threshold. SW2 in the ON position provides a 15% (+/-3%) differential. In the OFF position, it provides a 25% (+/-3%) differential. SW2 can be selected at anytime and does not affect the threshold setting. Current in-range closes the sensor contact. Current above or below range opens the sensor contact.
Main Features
- Adjustable 75-150 Amp Range
- 30-Second Self-Calibration
- Safe Calibration with SW1
- 15% or 25% Differential with SW2
- In-Range Current Closes Sensor Contact
General Information
Specifications
ADI Part Number FY-RIBXGTA Brand Name Functional Devices Manufacturer Functional Devices, Inc Manufacturer Part Number RIBXGTA Product Model RIBXGTA Product Name Current Switch, Split Core, Adjustable, 0.75-150 Amp, Terminal Product Type Current Switch
Input Voltage 600V AC